The modular system, 4×analog input – Lenze EPM−T9XX Modular system User Manual

Page 72

Advertising
background image

4×analog input

4

The modular system

4.14

L

4.14−4

EDSPM−TXXX−9.0−11/2009

Type

4×analog input

Voltage supply

DC 5 V / 280 mA (via backplane bus)

Connectable cable cross−section

£ 2.5 mm

2

(

³ AWG 14)

Analog inputs

Number

4

Input area

Voltage

−10 ... +10 V
−4 ... +4 V
−400 ... +400 mV
0 ... +50 mV

Information on tolerances
can be found in the chapter
"Parameter setting"

Current

−20 ... +20 mA
+4 ... +20 mA

Resistance

60

W, 600 W, 3 kW,6 kW

Resistor, temperature−dependent

PT100, PT1000, Ni100,
NI1000

Thermal element

J, K, N, R, S, T

Input resistance

Voltage range

2 M

W

Current range

50

W

Delay times

Conversion time/resolution

Conversion rate

[Hz]

3.7

7.5

15

30

60

123

168

202

Processing time per channel

[ms]

290

150

84

54

36

28

26

26

Resolution

[bit]

16

16

16

16

15

14

12

10

Electrical isolation from backplane bus

Yes, via optocouplers

Communication

Input data

8 bytes (2 bytes per analog input)

Parameter data

10 bytes

Diagnostic data

4 bytes

Dimensions

Width

25.4 mm

Height

76.0 mm

Depth

76.0 mm

Weight

100 g

Order number

EPM−T310

Technical data

Advertising