13 parameter setting via profibus−dp – Lenze EPM−T9XX Modular system User Manual

Page 478

Advertising
background image

Parameterising 2/4xcounter module

2 × 32 bit counter with GATE and RES edge−triggered (modes 31 and 32)

13

Parameter setting via PROFIBUS−DP

13.2

13.2.16

L

13.2−44

EDSPM−TXXX−9.0−11/2009

13.2.16

2 × 32 bit counter with GATE and RES edge−triggered (modes 31 and 32)

epm−t154

Fig. 13.2−61

Terminal assignment of the 2/4xcounter in the modes 31 and 32

In the modes 31 to 32, two 32−bit counters are available, which are controlled via
a gate signal (gate). A starting value and a comparison value can be assigned to
each counter.

The modules differ in having different counting directions:

Mode 31: Upcounter.
Mode 32: Downcounter

A LOW/HIGH edge at input IN1 / IN04 (RES

û

) clears the counter.

If a HIGH level is applied to input IN3 / IN6 (GATE), the counter is incremented or
decremented by 1 with each LOW/HIGH edge.

Once the counter reaches the value loaded in the "Compare" register, output
OUT0 / OUT1 is set to HIGH level for at least 100 ms, with the counter continuing
its task.

Terminal assignment

RES

û signal

GATE/CLK signal

OUT signal