Parameterising 1xcounter/16xdigital input module

Parameterising digital input filters

13

Parameter setting via PROFIBUS−DP

13.4

13.4.8

L

13.4−14

EDSPM−TXXX−9.0−11/2009

13.4.8

Parameterising digital input filters

Counting pulses at the inputs E.0 and E.1 must have a specific minimum length to
be evaluated. The pulse length T

Pulse

is set via digital input filters.

l

Lenze setting: T

Pulse

= 2.5

ms

l

Filter factor A is defined via byte 1 of the parameter data:

– Permissible values: 0 ... 255 (Lenze setting: 0)

l

Filter factor B is defined via byte 2 of the parameter data:

– Permissible values: 0 ... 255 (Lenze setting: 0)

T

Pulse

³ (Filter factor A + 1) × (Filter factor B + 1) × 2.5 ms

Filter factor settings:

l

Filter factor A = 3

l

Filter factor B = 0

Counting pulses with the following minimum length are evaluated:

T

Pulse

³ (3 + 1) Ч (0 + 1) Ч 2.5 ms

T

Pulse

³ 10 ms

Formula for calculation

Example