3 alarm messages, Alarm messages, Networking via profibus−dp – Lenze EPM−T9XX Modular system User Manual

Page 280: Diagnostics alarm messages

Advertising
background image

Diagnostics

Alarm messages

10

Networking via PROFIBUS−DP

10.6

10.6.3

L

10.6−6

EDSPM−TXXX−9.0−11/2009

10.6.3

Alarm messages

)

Note!

Alarm messages are only available in power section DP−V1.

Alarm messages supply information on the type and the cause of the alarm. An
alarm message has a maximum length of 20 bytes. Diagnostic messages can each
be transmitted with one alarm message.

There are two types of alarm messages:

l

Diagnostic alarm

l

Process alarm

In the case of a process alarm (e.g. open circuit), the additional alarm information
is 4 bytes long. The data is module−specific. For further information, refer to the
corresponding module description.

)

Note!

In the case of a diagnostic event for channel/channel group 0 of a
module, either the channel or the module is defective.

l

This event is transmitted even if the diagnostics are not
activated for channel/channel group 0 of the module.

The alarm status is contained in bytes 1 to 5:

Byte

Assignment

Byte 1

Bit 5 ... 0

010100

Number of assigned bytes

Bit 7, 6

Code for device−specific diagnostics

Byte 2

Bit 6 ... 0

Alarm type
0000001

Diagnostic alarm

0000010

Process alarm

Bit7

Alarm code

Byte 3

Bit 7 ... 0

Module which triggered alarm
00000001

Module on slot 1

00000010

Module on slot 2

00000011

Module on slot 3

...

...

00001000

Module on slot 8

Byte 4

Bit 1, 0

00

Process alarm

01

Incoming diagnostic alarm

10

Outgoing diagnostic alarm

11

Reserved

Bit 2

0

Fix

Bit 7 ... 3

00000000

Alarm sequence 1

00000001

Alarm sequence 2

00000010

Alarm sequence 3

...

...

00000111

Alarm sequence 8

Description

Process alarm

Diagnostic alarm