1 can gateway, Can gateway, The modular system – Lenze EPM−T9XX Modular system User Manual

Page 31: Up to 32 modules can be connected to a can gateway, Address and baud rate setting via coding switch, Led for status display

Advertising
background image

CAN gateway

4

The modular system

4.1

L

4.1−1

EDSPM−TXXX−9.0−11/2009

4.1

CAN gateway

The CAN gateway is the interface between the process level and the master bus
system. The control signals at the process level are transmitted by the electronic
modules. These modules are connected with the CAN gateway via the backplane
bus (EPM−T9XX). CAN gateway and the connected electronic modules
communicate via the backplane bus. A configuration is not required.

l

Up to 32 modules can be connected to a CAN gateway

l

Integrated power supply unit for the internal voltage supply and the voltage
supply of the connected electronic modules

– Power supply unit is fed via an external DC voltage source

l

Connection to the system bus (CAN) / CANopen via a 9−pole Sub−D plug

l

Address and baud rate setting via coding switch

l

The baud rate is stored permanently in an EEPROM in the module

l

LED for status display

PW

ER

RD

BA

ADR.

DC
24V

+

-

1

2

X1

EPM

– T1

10

xx.xx

0

1

0

1
2
3

epm−t009

Fig. 4.1−1

Overview of CAN gateway

0

LED for status display

1

9−pole Sub−D plug for connection to the system bus (CAN)

2

Coding switch to set address and baud rate

3

External voltage supply connection

View

Pin

Assignment

Explanation

1

2

3

4

5

6

7

8

9

1

Not assigned

2

CAN−LOW

Data line

3

CAN−GND

Data ground

4

Not assigned

5

Not assigned

6

Not assigned

7

CAN−HIGH

Data line

8

Not assigned

epm−t023

9

Not assigned

Description

Features

Overview

Connecting system
bus (CAN)/CANopen

Advertising