Input data / output data

12

Parameter setting via system bus (CAN) / CANopen

12.4

12.4.2

L

12.4−5

EDSPM−TXXX−9.0−11/2009

The counter 0 is to be set with the figure 26959382. To make the representation
simpler, the figure is given in a hexadecimal format.

Selection

Node address

2

Baud rate

500 kbaud

COB−ID Rx PDO 2 (I1401/1)
COB−ID Rx PDO 3 (I1402/1)
COB−ID Tx PDO 2 (I1801/1)
COB−ID Tx PDO 3 (I1802/1)

282

h

202

h

281

h

182

h

Event time (I1801/1)

64

h

Mode (I3001/1)

00

h

epm−t140

Fig. 12.4−3

Setting the counter content for the 2/4xcounter

1. Transmit the 1. Rx PDO with the counter setting value.

2. For accepting the counter setting value transmit the 2. Rx PDO:

Control byte = 30

h

.

3. The current count value is output via the 1. Tx PDO.

Example