Type

PROFIBUS GatewayECO

Voltage supply

Voltage

DC 24 V (DC 20.4 ... 28.8 V)

Max. current consumption PROFIBUS
GatewayECO

0.3A

Max. current consumption of electronic
modules

0.8 mA

Connectable cable cross−section

£ 2.5 mm

2

(

³ AWG 14)

Communication

Communication profile
(DIN 19245 Part 1 and Part 3)

PROFIBUS−DP

Communication media

RS485

Network topology

Without repeater: line
With repeater: line or tree

PROFIBUS−DP nodes

Slave

Baud rate for line type A
(EN 50170)

9.6 kBit/s ... 12 MBit/s (automatic recognition)

Max. number of nodes

Standard

32

1 bus segment

With repeater

126

Max. line length per bus segment

1200 m

Depending on the baud rate and the used line type

Electrical isolation from field bus

Yes, via optocouplers

Diagnostics function

Stores the last 100 diagnoses with time stamp in the flash ROM

Connectable electronic modules

Max. number of electronic modules

8

The number can be limited by the maximum
current consumption of electronic modules.

Max. number of digital and analog
input/output modules

8

Process data for PROFIBUS−DP−V0

Max. input data

244 bytes

Max. output data

244 bytes

Process data for PROFIBUS−DP−V1

Max. input data

240 bytes

Max. output data

240 bytes

Dimensions

Width

25.4 mm

Height

76.0 mm

Depth

76.0 mm

Weight

80 g

Order designation

EPM−T121

Technical data