background image

Parameterising 1xcounter/16xdigital input module

Parameter data

13

Parameter setting via PROFIBUS−DP

13.4

13.4.1

L

13.4−1

EDSPM−TXXX−9.0−11/2009

13.4

Parameterising 1xcounter/16xdigital input module

13.4.1

Parameter data

l

For the 1xcounter/16xdigital input, 3 bytes of parameter data are available.
The parameter data can be used to assign a mode to the internal counter
and to configure the digital input filter.

l

The module can be parameterised with the configuration tool or via slot and
index.

– To set the parameters via slot and index, the function blocks SFB 52 (read)

and SFB 53 (write) are required.

(

10.5−3)

Slot number

Index

Access

Description

1 ... 32

00

h

R

Read out diagnostic data record 0

W

Write parameters to the module

01

h

R

The corresponding diagnostic data record of the electronic module can be
read out via the index.

·

Example:

– Index 01

h

: read out diagnostic data record 1

– Index 02

h

: read out diagnostic data record 2

F1

h

R

Read out the module parameters

F2

h

R

Read out the process image of the module

R = read

W = write

The parameter data follows the assignment below:

Byte

Assignment

Lenze setting

0

Counter mode

00

h

Encoder with 4 edges

00

h

01

h

32−bit counter

02

h

Clock up/clock down evaluation

03

h

Measuring the frequency

04

h

Measuring the period

05

h

... FF

h

Reserved

1

Filter factor A

0 ... 255

Configuration of the digital input filters for
counter inputs E.0 and E.1

00

h

2

Filter factor B

0 ... 255

00

h