8 signal functions of 4xanalog output, Signal functions of 4xanalog output – Lenze EPM−T9XX Modular system User Manual

Page 311

Advertising
background image

Parameterising analog modules

Signal functions of 4xanalog output

12

Parameter setting via system bus (CAN) / CANopen

12.3

12.3.8

L

12.3−13

EDSPM−TXXX−9.0−11/2009

Paramete
r bytes
2/3/4/5

Tolerance

Format

1)

Signal range

Signal function

39

h

Current
measurement

4 ... 20
mA

4.00
0

{0.01 mA}

{1

dec

}

20.00

16384

S5

Two’s

complement

±0.2 %

2)

±0.5 %

3)

Min.

Limit

values

Max.

0.8 mA
−3277

dec

+24.00 mA

+20480

dec

3A

h

3Bh

Current
measurement

±20 mA

−20.00
−16384

{0.01 mA}

{1

dec

}

+20.00

16384

S5

Two’s

complement

±0.1 %

2)

±0.2 %

3)

Min.

Limit

values

Max.

−25.00 mA
−20480

dec

+25.00 mA

+20480

dec

FF

h

Analog input deactivated

1)

Format of the input data (

12.3−7).

2)

Tolerance of the input range at an ambient temperature of 25 °C.

3)

Tolerance of the input range across the entire admissible temperature range.

Lenze setting of the signal function in parameter bytes 2 and 3 or 4 and 5: 3A

h

12.3.8

Signal functions of 4xanalog output

)

Note!

In the event of an overflow or underflow, wrong values are output.
Strong signal jumps with sign reversal may occur.

Paramete
r bytes
2/3/4/5

Signal function

Signal range

Format

1)

Tolerance

00

h

13

No signal emitted at output

01

h

Voltage signal
output

±10 V

−10.00
−16384

{0.01V}

{1

dec

}

+10.00

16384

S5

Two’s

complement

±0.2 %

2)

3)

Min.

Limit

values

Max.

−12.50 V
−20480

dec

+12.50 V
20480

dec

02

h

Voltage signal
output

+1 ... +5
V

1.0
0

{0.1V}

{1

dec

}

+5.0

16384

S5

Two’s

complement

±0.4 %

2)

3)

Min.

Limit

values

Max.

0.0
−4096

dec

+6.0 V

20480

dec

05

h

Voltage signal
output

0... +10 V 0.0

0

{0.1V}

{1

dec

}

+10.0

16384

S5

Two’s

complement

±0.3 %

2)

3)

Min.

Limit

values

Max.

0.0
0

+12.5 V

20480

dec

Advertising