background image

16×dig. I/O compact (single−wire conductor)

5

The compact system

5.2

L

5.2−6

EDSPM−TXXX−9.0−11/2009

X4/1

X4/2

X3/10

X3/9

X3/8

X3/7

X3/6

X3/5

X3/4

X3/3

X3/2

X3/1

X4/3

X4/4

X4/5

X5/6

X4/7

X4/8

X4/9

X4/10

Z

Z

Z

Z

Z

Z

+

X1

PE

µC

+

+

+

+

DC 24 V

(DC +18 … +35 V)

0

epm−t052

Fig. 5.2−5

Wiring diagram of 16×dig. I/O compact (single−wire conductor)

0

Emergency−off switch

Z

Load

(

Stop!

If the voltage supply (DC 24 V) fails, the module will malfunction:

l

Switched outputs carry voltage if one input is assigned with a
HIGH level,

l

The module can be destroyed since the outputs are not
resistant to short circuits anymore.

The emergency−off switch ensures that when being operated the
outputs do not carry any voltage and the inputs are not assigned
with a HIGH level.