Parameterising analog modules

Parameter data

13

Parameter setting via PROFIBUS−DP

13.1

13.1.1

L

13.1−4

EDSPM−TXXX−9.0−11/2009

l

For the 4xanalog input/output module, up to 8 bytes of parameter data are
available. The following are defined via the parameter data

– The signal function for each input or output (current measurement, voltage

measurement, temperature measurement, or current signal output, voltage
signal output),

– The module error behavior,

– The conversion speed.

l

The module can be parameterised with the configuration tool or via slot and
index.

– To set the parameters via slot and index, the function blocks SFB 52 (read)

and SFB 53 (write) are required.

Slot number

Index

Access

Description

1 ... 32

00

h

R

Read out diagnostic data record 0

W

Write parameters to the module

01

h

R

The corresponding diagnostic data record of the electronic module can be
read out via the index.

·

Example:

– Index 01

h

: read out diagnostic data record 1

– Index 02

h

: read out diagnostic data record 2

F1

h

R

Read out the module parameters

F2

h

R

Read out the process image of the module

R = read

W = write

4xanalog input/output module