Communication

Cyclic data transfer

10

Networking via PROFIBUS−DP

10.3

10.3.2

L

10.3−2

EDSPM−TXXX−9.0−11/2009

10.3.2

Cyclic data transfer

The data communication with PROFIBUS−DP−V0 includes cyclic diagnostics as
well as cyclic process data and parameter data transfer.

Master

(DPM 1)

Slave

buffer receive

Communications

processor

PA

buffer send

PE

0

1



‚

epm−t228

Fig. 10.3−1

DP cycle and cycle of backplane bus

0

Backplane bus with transmit and receive buffer

1

Input / output modules

PO: process image of outputs

PI: process image of inputs

 PROFIBUS cycle
‚ Backplane bus cycle

During a backplane bus cycle

l

the input data (PI) on the inputs is collected and transmitted to the transmit
buffer (buffer send),

l

the output data (PO) of the receive buffer (buffer receive) is written to the
outputs.

During a PROFIBUS cycle, the master successively addresses all its assigned
slaves with a DataExchange. During a DataExchange, the memory areas assigned
to the PROFIBUS are transmitted.

l

The data of the PROFIBUS input area is transmitted to the receive buffer
(buffer receive).

l

The data of the transmit buffer (buffer send) is transmitted to the PROFIBUS
output area.

Backplane bus cycle

PROFIBUS cycle