13 parameter setting via profibus−dp – Lenze EPM−T9XX Modular system User Manual

Page 434

Advertising
background image

Parameterising analog modules

Signal functions of 4xanalog input /output

13

Parameter setting via PROFIBUS−DP

13.1

13.1.10

L

13.1−22

EDSPM−TXXX−9.0−11/2009

Paramete
r bytes
4/5

Tolerance

2)

Format

1)

Signal range

Signal function

06

h

Current signal
output

0 ... 20
mA

0.00
0

{0.01 mA}

{1

dec

}

+20.00

+16384

S5

Two’s

complement

±0.6 %

Min.

Limit

values

Max.

0.00
0

+25.00 mA

+20480

dec

0Bh

Current signal
output

±20 mA

−20.00
−27648

{0.01 mA}

{1

dec

}

+20.00

+27648

S7

Two’s

complement

±0.3 %

Min.

Limit

values

Max.

−23.52 mA
−32512

dec

+23.52 mA

+32511

dec

0C

h

Current signal
output

4 ... 20
mA

+4.00
0

{0.01 mA}

{1

dec

}

+20.00

+27648

S7

Two’s

complement

±0.8 %

Min.

Limit

values

Max.

0.00
−6912

dec

+22.81 mA

+32511

dec

0E

h

Current signal
output

0 ... 20
mA

0.00
0

{0.01 mA}

{1

dec

}

+20.00

+27648

S7

Two’s

complement

±0.6 %

Min.

Limit

values

Max.

0.00
0

+23.52 mA

+32511

dec

FF

h

Analog output is switched off

1)

Format of the output data (

13.1−6).

2)

Tolerance of the output range at an ambient temperature of 25 °C.