4 SERVOPACK Specifications and Dimensional Drawings

4-6

Orientation

Install the SERVOPACK perpendicular to the wall as shown in the figure. The SERVOPACK must be oriented
this way because it is designed to be cooled by natural convection or a cooling fan.
Secure the SERVOPACK using two to four mounting holes. The number of holes depends on the capacity.

Installation

Follow the procedure below to install multiple SERVOPACKs side by side in a control panel.

SERVOPACK Orientation

Install the SERVOPACK perpendicular to the wall so the front panel containing connectors faces outward.

Cooling

As shown in the figure above, allow sufficient space around each SERVOPACK for cooling by cooling fans
or natural convection.

Side-by-side Installation

When installing SERVOPACKs side by side as shown in the figure above, allow at least 10 mm (0.39 in)
between and at least 50 mm (1.97 in) above and below each SERVOPACK. Install cooling fans above the
SERVOPACKs to avoid excessive temperature rise and to maintain even temperature inside the control
panel.

Environmental Conditions in the Control Panel

Ambient Temperature:0 to 55

°C (32 to 131° F)

Humidity: 90

% RH or less

Vibration: 4.9 m/s

2

Condensation and Freezing: None
Ambient Temperature for Long-term Reliability: 45

°C (113 °F) or less

Voltage
Resistance Test

Conduct voltage resistance tests under the following conditions.

• Voltage: 1500 Vrms AC for one minute
• Braking current: 30 mA or more
• Frequency: 50 or 60 Hz
• Voltage applied points

For SGDH-††AE SERVOPACKs : Between the ground terminals and the point where the terminals L1,

L2, (L3), L1C, L2C, U, V, W are connected.

For SGDH-††DE SERVOPACKs : Between the neutral terminals and the point where the terminals L1,

L2, L3, U, V, W are connected.

Ventilation

Wall

Cooling fan

Cooling fan

30 mm
(1.18 in) min.

10 mm
(0.39 in) min.

50 mm (1.97 in) min.

50 mm (1.97 in) min.