7.5.2 Wiring for Noise Control

7-34

(3) Using Noise Filters

Use an inhibit type noise filter to prevent noise from the power supply line. The following table lists recom-
mended noise filters for each SERVOPACK model.

Install a noise filter on the power supply line for peripheral equipment as necessary.

„

Precautions when using noise filter

Always observe the following installation and wiring instructions. Incorrect use of a noise filter halves its
benefits.
1. Do not put the input and output lines in the same duct or bundle them together.

Voltage

SERVOPACK Model

Recommended Noise Filters

Model

Specifications

Manufacturer

Single-phase
200 V

SGDH-A5AE to -02AE

FN2070-6/07

Single-phase 250 VAC, 6A

SCHAFFNER

SGDH-04AE

FN2070-10/07

Single-phase 250 VAC, 10A

Three-phase
200 V

SGDH-05AE

FN258L-7/07

Three-phase 480 VAC, 7A

SGDH-08AE to -20AE

FN258L-16/07

Three-phase 480 VAC, 16A

SGDH-30AE

FN258L-30/07

Three-phase 480 VAC, 30A

SGDH-50AE

FMAC-0934-5010 Three-phase 440 VAC, 50A

SCHURTER
(formely
TIMONTA)

SGDH-75AE

FMAC-0953-6410 Three-phase 440 VAC, 64A

Three-phase
400 V

SGDH-05DE to -15DE

FN258L-7/07

Three-phase 480 VAC, 7A

SCHAFFNER

SGDH-20DE, -30DE

FN258L-16/07

Three-phase 480 VAC, 16A

SGDH-50DE, -75DE

FS5559-35-33

Three-phase 480 VAC, 35A