7 Wiring

7.2.3 Typical Main Circuit Wiring Examples

7-20

(3) Three-phase 400 V

„

Designing a Power ON Sequence

Note the following points when designing the power ON sequence.

• Design the power ON sequence so that main circuit power supply is turned OFF when a servo alarm signal

is output. See the previous circuit figure.

• When designing the power ON sequence, note that the SERVOPACK will output (1Ry is OFF) a servo

alarm signal for two seconds or less when the control power is turned ON. And, use this relay to turn OFF
the main power supply to the SERVOPACK

.

• Select the power supply specifications for the parts in accordance with the input power supply.

„

Harmonic Suppression

If another device requires for harmonic suppression, connect the DC reactor to the DC main circuit side on
the SERVOPACK. For connecting examples, refer to 7.5.5 DC Reactor for Harmonic Suppression.

L1

24V

24-VDC

power supply

+

SGDH-††DE

0 V

24

1Ry

ALM+

ALM

31

32

1D

1KM

1Ry

1KM

1SUP

1Ry

1KM

L2
L3
B2
B3

0V

CN1

1QF

R S T

1PL

1QF

FIL

1KM

FIL

+24V

+

1

+

2

U

V

W

M

PG

SERVOPACK

(For servo

alarm display)

OFF

ON

Main circuit

power supply

Main circuit

power supply

: Molded-case circuit breaker
: Noise filter
: Magnetic contactor

: Indicator lamp
: Surge suppressor
: Flyweel diode

1PL
1SUP
1D

1Ry

: Relay

Serial

converter

unit

Linear servomotor

Linear scale

Properly treat the end of shielded wire.

IMPORTANT

Control power

supply

Servo alarm (ALM)

output signal

2.0 s max.