6.8 Peripheral Devices

6-23

6

6.8.7 Molded-case Circuit Breaker (MCCB)

Note the following descriptions when selecting a molded-case circuit breaker.

„

Circuit Breakers

• Select a breaker for inverters.
• High-frequency current leaks from the servomotor armature because of switching operations inside the SER-

VOPACK.

(1) Maximum Input Current

• The instantaneous maximum output of SERVOPACK is approximately 3 times of the rated output for

maximum 3 seconds. Accordingly, select a circuit breaker whose operating time is 5 seconds or more at
300% of SERVOPACK rated current.
The general-purpose and low-speed acting molded-case circuit breakers are applicable.

• The power supply capacity per SERVOPACK when using a servomotor is described in 2.6.2 Molded-case

Circuit Breaker and Fuse Capacity. Select a circuit breaker with the capacity larger than the effective
load current (when using multiple SERVOPACKs) calculated from the total power supply capacity.

• The power consumption of other controllers must be considered when selecting a circuit breaker.

(2) Inrush Current

• Refer to 2.6.2 Molded-case Circuit Breaker and Fuse Capacity for SERVOPACK inrush current.
• The allowable inrush current for a low-speed acting circuit breaker is approximately 10 times of the rated

current for 0.02 seconds.

• When turning ON multiple SERVOPACKs simultaneously, select a molded-case circuit breaker with the

allowable current for 20 ms larger than the total inrush current shown in 2.6.2 Molded-case Circuit
Breaker and Fuse Capacity
.