9.11 Limiting Force

9-69

9

9.11.2 External Force Limit (Output Force Limiting by Input Signals)

This function allows the force to be limited at specific times during machine operation, for example, during press
stops and hold operations for robot workpieces.
An input signal is used to enable the force limits previously set in parameters.

(1) Related Parameters

Note: The setting unit is a percentage of rated force (i.e., the rated force is 100%).

(2) Input Signals

Pn404

Forward External Force Limit

Setting Range

Setting Unit

Factory Setting

Setting Validation

0 to 800

%

100

Immediately

Pn405

Reverse External Force Limit

Setting Range

Setting Unit

Factory Setting

Setting Validation

0 to 800

%

100

Immediately

Speed

Position

Force

Speed

Position

Force

Type Signal

Name

Connector Pin

Number

Setting

Meaning

Limit Value

Input /P-CL

CN1-45
(Factory Setting)

ON (low level)

Forward external force limit
ON

The value set in Pn483 or
Pn404 (whichever is smaller)

OFF (high level)

Forward external force limit
OFF

Pn483

Input /N-CL

CN1-46
(Factory Setting)

ON (low level)

Reverse external force limit
ON

The value set in Pn484 or
Pn405 (whichever is smaller)

OFF (high level)

Reverse external force limit
OFF

Pn484

When using this function, make sure that there are no other signals allocated to the same terminals as /P-CL and /N-CL.
When multiple signals are allocated to the same terminal, the signals are handled with OR logic, which affects the ON/OFF
state of the other signals. Refer to 8.3.2 Input Circuit Signal Allocation

.