12.2 Calculating the Required Capacity of Regenerative Resistors

12-5

12

Note: The model with (-M) is the combination model with a standard-type coil assembly and a

high-force-type magnetic way.

Fig. 12.1 Operating Conditions for Allowable Regenerative Frequency Calculation

Use the following equation to calculate the allowable frequency for regenerative mode operation.

SGLTW-

20A170A

8

Twice of coil

assembly mass

20A320A

4

20A460A

2

35A170A

6

35A320A

2

35A460A

2

35A170H

3

35A320H

1

50A170H

4

50A320H

1

40A400B

1

Linear Servomotor Model

Allowable Frequencies in

Regenerative Mode (times/min.)

Load Condition

(Including Coil

Assembly)

Speed reference

Servomotor speed

Servomotor-generated force

Regene-

ration

mode

T

(Operating cycle)

Allowable frequency = 1/T (times/min)

Maximum speed

Maximum force

0

Maximum force

0

0

t

t

t

Allowable frequency =

×

n = / 15

Allowable frequency in regenerative mode (times)

n

n = / 3

W

W

M

W

W

M

Peak speed

Used speed

2

times/min

y

n For SGLGW,

y

W

M

Linear servomotor coil assembly mass

y

W Load mass (including coil assembly)

For SGLTW and SGLFW,

excluding SGLTW-40 and -80)

n =

W

W

M

For SGLTW-40 and -80,