2 analog signal input timing, 2 analog signal input timing -3, Important – Yaskawa SGDH Linear Sigma Series User Manual

Page 123

Advertising
background image

5.2 Analog Signal Input Timing

5-3

5

5.2 Analog Signal Input Timing

The following figure shows the input timing of the analog signals.
When the cos and sin signals are shifted 180 degrees, the differential signals are the /cos and /sin signals. The
specifications of the cos, /cos, sin, and /sin signals are identical except for the phase.
Input the signals Ref and /Ref so that they shall cross each other as shown in the figure because they are input
into the converter. When they are crossed, the output data will be counted up.

* If the analog signal amplitude declines to about 0.35 V because of differential amplitude, the serial con-

verter outputs an alarm.

„

Precautions

1. Never perform insulation resistance and withstand voltage tests.
2. When analog signals are input to the serial converter unit, noise influence on the analog signals affects

the unit’s ability to output correct position information. The analog cable must be as short as possible
and shielded.

3. Use the device in an environment free from hydrogen sulfide (H

2

S) and other hazardous gases.

4. Do not connect or disconnect the unit while power is being supplied, or the unit may be damaged.
5. When using multiple axes, use a shield cable for each axis. Do not use a shield cable for multiple axes.

Zero Point

Count up direction

cos

/cossin/sin

Input voltage range:
1.5 V to 3.5V

Ref

/Ref

Input voltage range:
1.5 V to 3.5V

100%

45

q

5 to 75%

5 to 75%

0.2 V min.

0.2 V min.

0.2

VQ

0.6 V

cos

㧔A+㧕

/cos

㧔A-㧕

sin

㧔B+㧕

/sin

㧔B-㧕

/Ref

㧔R-㧕

Ref

㧔R+㧕

IMPORTANT

Advertising