9.8 Operating Using Position Control

9-59

9

9.8.7 Reference Pulse Inhibit Function (INHIBIT)

(1) Description

This function inhibits the SERVOPACK from counting input pulses during position control. The servomotor
remains locked (clamped) while pulse are inhibited.

(2) Setting Parameters

(3) Setting Input Signals

Pn000.1

Pn000=n.††1†

Pn000=n.††B†

OFF

ON

+

-

/P-CON (/INHIBIT)

/P-CON

(/INHIBIT)

Error
counter

Reference pulse

Feedback pulse

SERVOPACK

Parameter

Meaning

Pn000

n.††B†

Control mode selection: Position control (pulse train reference)

Inhibit

„ Inhibit (INHIBIT) switching condition

x /P-CON (/INHIBIT) signal ON (low level)

Type

Signal Name

Connector Pin

Number

Setting

Meaning

Input

/P-CON

CN1-41
(Factory setting)

ON (low level)

Turns the INHIBIT function ON.
(Inhibits the SERVOPACK from counting refer-
ence pulses.)

OFF (high level)

Turns the INHIBIT function OFF.
(Counts reference pulses.)

(Input)

(/INHIBIT)

Must be allocated
CN1-††

ON (low level)

Turns the INHIBIT function ON.
(Inhibits the SERVOPACK from counting refer-
ence pulses.)

OFF (high level)

Turns the INHIBIT function OFF.
(Counts reference pulses.)

These input signals enable the inhibit function.
Either the /P-CON or the /INHIBIT signal can be used to switch the inhibit signal. The input signal must be allocated in
order to use the /INHIBIT signal. Refer to 8.3.2 Input Circuit Signal Allocation.

ON

Reference pulse

OFF

t1

ON

t2

t1, t2

≤ 0.5 ms

Input reference pulses
are not counted
during this period.

/INHIBIT signal

(/P-CON)