5.4 MP2000 Series Machine Controller Parameter Details

5.4.2 Motion Setting Parameter Details

5-39

5

Motion Parameters

( 26 ) Zero Point Return

A typical example of a zero point return operation is shown below.

Refer to 7.2.3 Zero Point Return (ZRET) on page 7-15 for details.

OW

3C

Zero Point Return Method

Setting Range

Setting Unit

Default Value

0 to 19

0

Description

Set the operation method when the Zero Point Return (ZRET) motion command is executed.

With an incremental encoder, there are 17 different methods that can be performed for the Zero Point Return operation.

Refer to 7.2.3 Zero Point Return (ZRET) on page 7-15 for information on each method.

With an absolute encoder, the axis is returned to the zero point of the machine coordinate system regardless of which
method is being used.

OW

3D

Width of Starting Point Position Output

Setting Range

Setting Unit

Default Value

0 to 65535

Reference unit

100

Description

Set the width in which the Zero Point Position bit (monitoring parameter IW

0C, bit4) will be ON.

OL

3E

Approach Speed

Setting Range

Setting Unit

Default Value

−2

31

to 2

31

−1

Depends on the

speed unit set in

Function Setting 1

(setting parameter

OW

03, bits 0 to

3)

1000

Description

Set the approach speed for a zero point return operation after the deceleration LS is passed.

The setting unit for this parameter depends on the Speed Unit Selection (OW

03, bits 0 to 3), but the

result of applying the speed unit setting is not shown here.

OL

40

Creep Rate

Setting Range

Setting Unit

Default Value

−2

31

to 2

31

−1

Depends on the

speed unit set in

Function Setting 1

(setting parameter

OW

03, bits 0 to

3)

500

Description

Set the creep speed for a zero point return operation after the ZERO signal is detected.

The setting unit for this parameter depends on the Speed Unit Selection (OW

03, bits 0 to 3), but the

result of applying the speed unit setting is not shown here.

OL

42

Zero Point Return Travel Distance

Setting Range

Setting Unit

Default Value

−2

31

to 2

31

−1

Reference unit

0

Description

Set the distance from where the signal is detected to the zero point position.

Position

Phase

Speed Torque

Position

Phase

Speed Torque

Position

Phase

Speed Torque

Position

Phase

Speed Torque

Position

Phase

Speed Torque

Speed

Start

(OL

40)

(OL

42)

DEC signal

Phase-C pulse

Creep Rate

Zero Point Return

Travel Distance

Width of

Starting

Point

Position

Output

(OL

3E)

Approach Speed

(OL

10)

Speed Reference Setting

Position