3 ) warning – Yaskawa JAPMC-MC2300 User Manual

Page 116

Advertising
background image

5.4 MP2000 Series Machine Controller Parameter Details

5.4.3 Motion Monitoring Parameter Details

5-44

( 3 ) Warning

IL

02

Warning

Range

Unit

Description

Bit 0

Excessive Deviation

0: In normal deviation range
1: Abnormal deviation detected

This bit turns ON if the following error exceeds the value set for the Error Count Alarm Detection (setting
parameter OL

22) when Excessive Deviation is set to be treated as an warning by setting the Excessive

Deviation Error Level Setting to 0 in Mode Setting 1 (setting parameter OW

01, bit 0).

Bit 1

Set Parameter Error

0: In setting range
1: Outside setting range

This bit turns ON when one or more motion setting parameters is set outside the setting range. The number of
the parameter for which the value is out of range is stored as the Parameter Number when Range Over is
Generated (monitoring parameter IW

01).

Bit 2

Fixed Parameter Error

0: In setting range
1: Outside setting range

This bit turns ON when one or more motion setting parameters is set outside the motion fixed parameter setting
range. The number of the parameter is stored as the Parameter Number when Range Over is Generated (moni-
toring parameter IW

01).

Bit 4

Motion Command Set Error

0: Command setting normal
1: Command setting error

This bit turns ON when a motion command that cannot be used is set.

Bit B

Analog Adjust Not Ready Warning

0: Adjustment normally completed
1: Adjustment error

This bit turns ON for warning when the SVA-01 Module has not been correctly adjusted before shipment.