2 connection procedure for 24-v input cable – Yaskawa JAPMC-MC2300 User Manual

Page 37

Advertising
background image

2.4 SVA-01 Module Connections

2.4.2 Connection Procedure for 24-V Input Cable

2-11

2

Settings and Installation

2.4.2 Connection Procedure for 24-V Input Cable

Prepare a 0.2 mm

2

to 0.51 mm

2

(AWG24 to AWG20) twisted-pair cable. Use the following connection procedure.

1.

Remove the sheath to approximately 6.5 mm from the cable end.

2.

Remove the plug from the CN3 connector on the SVA-01 Module.

3.

Insert the bare core of the cable into the opening of the plug and then tighten the secrews to a tighten-

ing torque of approximately 0.2 to 0.25 N

x

m.

Pin No.

Signal

Name

Name

2

24V

+24 VDC input

1

0V

0V

Core

Sheath

6.5 mm

+ side (pin number 2)

− side (pin number 1)