Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 120

Advertising
background image

120

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Starter Enclosure

Bit 0 = IP67
Bit 1 = Reserved
Bit 2 = Sil3/Cat4
Bit 3…15 = Reserved

Parameter Number

59

Access Rule

GET

Data Type

WORD

Group

Basic Status

Units

Minimum Value

0

Maximum Value

4

Default Value

1

Starter Options

Bit 0 = Full Keypad
Bit 1 = Reserved
Bit 2 = Source Brake
Bit 3 = Reserved
Bit 4 = Reserved
Bit 5 = Reserved
Bit 6 = Reserved
Bit 7 = Reserved
Bit 8 = Reserved
Bit 9…15 = Reserved

Parameter Number

60

Access Rule

GET

Data Type

WORD

Group

Basic Status

Units

Minimum Value

0

Maximum Value

66535

Default Value

0

Last PR Fault

0 = None
1 = Hardware Short Circuit
2 = Software Short Circuit
3 = Motor Overload
4 = Reserved
5 = Phase Loss
6…12 = Reserved
13 = Control Power Loss
14 = Control Power Fuse
15 = I/O Short
16 = Output Fuse
17 = Overtemp
18 = Reserved
19 = Phase Imbalance
20 = Reserved
21 = A3 Power Loss
22 = Internal Comm
23…26 = Reserved
27 = MCB EEPROM
28 = Base EEPROM
29 = Reserved
30 = Wrong Base
31 = Wrong CTs
32…100 = Reserved

Parameter Number

61

Access Rule

GET

Data Type

UINT

Group

Basic Status

Units

Minimum Value

0

Maximum Value

100

Default Value

0