➊ The Fault text for this error is not return by the device, and is only reported as “Fault 45”.

DPI Alarm Object

CLASS CODE 0x0098

The following class attributes will be supported:

24

Power Loss

Drive DC Bus Voltage remained below 85% of nominal bus voltage.

25

Under Voltage

DC Bus Voltage fell below the minimum value.

26

Over Voltage

DC Bus Voltage exceeded the maximum value.

27

MCB EEPROM

This is a major fault which renders the ArmorStart inoperable.

28

Base EEPROM

This is a major fault which renders the ArmorStart inoperable.

29

Drive EEPROM

The drive EEPROM checksum checks have failed.

30

Wrong Base

The ArmorStart controller is connected to the wrong base type.

31

Fan RMP

The internal cooling fan is not running properly.

32

Power Unit

A major failure has been detected in the drive power section.

33

Drive I/O Brd

A failure has been detected in the drive control and I/O section.

34

Restart Retries

Automatic fault reset and run retries exceeded.

35

Drive Aux In Flt

The drive auxiliary input interlock is open inside the ArmorStart.

36

Analog Input

(PF Fault Code 29)

37

Drv Param Reset

Internal Drive Parameters (Parameters > 100) have been defaulted.

38

SCV Autotune

The drive automatic tuning function was either aborted or failed.

39

Source Brake

The source brake fuse has blown. Remove power and replace fuse.

40

Unknown Fault

41

DB1 Comm

Communication with an internal DB1 board has been lost.

42

DB1 Fault

A fault has been detected with the operation of the Dynamic Brake.

43

DB Switch Short

The Dynamic Brake switch is shorted.

44

Fault 44

45

Incompatible COMM

Device

The Software revision of the Drive is not compatible with the ArmorStart.

Table 50 Bulletin 284E

Fault Code

Fault Text

Help Text

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Class Revision

UINT

1

2

Get

Number of Instances

UINT

1

3

Set

Alarm Cmd Write

USINT

0=NOP, 1=Clear Fault, 2=Clear Flt Queue

74

Get

Alarm Instance Read

UINT

The instance of the Fault Queue Entry containing information
about the Fault that tripped the Device.

6

Get

Number of Recorded Faults

UINT

The number of Faults recorded in the Fault Queue.