Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Figure 69 - Boost Select
5
0.0 no IR
Constant Torque
6
0.0
7
2.5, CT (default for 5 Hp/4.0 kW Drive)
8
5.0, CT (default)
9
7.5, CT
10
10.0, CT
11
12.5, CT
12
15.0, CT
13
17.5, CT
14
20.0, CT
Start Boost
Sets the boost voltage (% of
Parameter 131 (Motor NP Volts)) and
redefines the Volts per Hz curve when
Parameter 184 (Boost Select) = 0
(Custom V/Hz) and Parameter 225
(Torque Perf Mode) = 0 (V/Hz)
Parameter Number
185
Related Parameters
131, 132, 134, 135, 184,
186…188, 225
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
1.1%
Minimum Value
0.0%
Maximum Value
25.0%
Default Value
2.5%
Table 23 - Boost Select Options
Options
Description
% P132 [Motor NP Hertz]
% P131 [Mot
or NP
Volts]
100
50
1/2 [Motor NP Volts]
1/2
[Motor NP Hertz]
4
3
2
1
0
50
100
Settings
5-14