Bulletin 280E/281E/284E Programmable Parameters Chapter 7

191

PWM Frequency

Sets the carrier frequency the PWM output waveform.
Figure 72 provides derating guidelines based on the PWM
frequency setting.

4.0 Hz

Drive Advanced Setup

192

Auto Rstrt Tries

Set the maximum number of times the drive attempts to reset a
fault and restart.

0

Drive Advanced Setup

193

Auto Rstrt Delay

Sets time between restart attempts when Parameter 192 (Auto
Rstrt Tries) is set to a value other than zero.

1.0 Secs

Drive Advanced Setup

194

Start At PowerUp

Enables/disables a feature that allows a Start or Run command to
automatically cause the drive to resume running at command
speed after the drive input is restored.

0 = Disabled

Drive Advanced Setup

195

Reverse Disable

Enables/disables the function that allows the direction of the
motor rotation to be changed.

0 = Disabled

Drive Advanced Setup

196

Flying Start En

Sets the condition that allows the drive to reconnect to a spinning
motor at actual RPM.

0 = Disabled

Drive Advanced Setup

197

Compensation

Enables/disables correction options that may improve problems
with motor instability.

1 = Electrical

Drive Advanced Setup

198

SW Current Trip

Enables/disables a software instantaneous (within 100 ms)
current trip.

0.0 (Disabled)

Drive Advanced Setup

199

Process Factor

Scales the output frequency value displayed by Parameter 110
(Process Display).

30.0

Drive Advanced Setup

200

Fault Clear

Resets a fault and clears the fault queue.

0 = Ready/Idle

Drive Advanced Setup

201

Program Lock

Protects parameters against change by unauthorized personnel.

0 = Unlocked

Drive Advanced Setup

202

Testpoint Sel

Used by Rockwell Automation field service personnel.

400

Drive Advanced Setup

203

Option not valid for Bulletin 284E ArmorStart.

204

Option not valid for Bulletin 284E ArmorStart.

205

Comm Loss Action

Selects the drive’s response to a loss of the communication
connection or excessive communication errors.

0 = Fault

Drive Advanced Setup

206

Comm Loss Time

Sets the time that the drive remain in communication loss before
implanting the option selected in Parameter 205 (Comm Loss
Action).

15.0 Secs

Drive Advanced Setup

207

Option not valid for Bulletin 284E ArmorStart.

208

Option not valid for Bulletin 284E ArmorStart.

209

Option not valid for Bulletin 284E ArmorStart.

210

Option not valid for Bulletin 284E ArmorStart.

211

Option not valid for Bulletin 284E ArmorStart.

212

Option not valid for Bulletin 284E ArmorStart.

213

Option not valid for Bulletin 284E ArmorStart.

214

Slip Hertz @ FLA

Compensates for the inherent slip in an induction motor. This
frequency is added to the commanded output frequency based
on motor current.

2.0 Hz

Drive Advanced Setup

Table 29 - Parameter Descriptions

Parameter

Number

Parameter

Name

Description