Bulletin 280E/281E/284E Programmable Parameters Chapter 7
191
PWM Frequency
Sets the carrier frequency the PWM output waveform.
Figure 72 provides derating guidelines based on the PWM
frequency setting.
4.0 Hz
Drive Advanced Setup
192
Auto Rstrt Tries
Set the maximum number of times the drive attempts to reset a
fault and restart.
0
Drive Advanced Setup
193
Auto Rstrt Delay
Sets time between restart attempts when Parameter 192 (Auto
Rstrt Tries) is set to a value other than zero.
1.0 Secs
Drive Advanced Setup
194
Start At PowerUp
Enables/disables a feature that allows a Start or Run command to
automatically cause the drive to resume running at command
speed after the drive input is restored.
0 = Disabled
Drive Advanced Setup
195
Reverse Disable
Enables/disables the function that allows the direction of the
motor rotation to be changed.
0 = Disabled
Drive Advanced Setup
196
Flying Start En
Sets the condition that allows the drive to reconnect to a spinning
motor at actual RPM.
0 = Disabled
Drive Advanced Setup
197
Compensation
Enables/disables correction options that may improve problems
with motor instability.
1 = Electrical
Drive Advanced Setup
198
SW Current Trip
Enables/disables a software instantaneous (within 100 ms)
current trip.
0.0 (Disabled)
Drive Advanced Setup
199
Process Factor
Scales the output frequency value displayed by Parameter 110
(Process Display).
30.0
Drive Advanced Setup
200
Fault Clear
Resets a fault and clears the fault queue.
0 = Ready/Idle
Drive Advanced Setup
201
Program Lock
Protects parameters against change by unauthorized personnel.
0 = Unlocked
Drive Advanced Setup
202
Testpoint Sel
Used by Rockwell Automation field service personnel.
400
Drive Advanced Setup
203
Option not valid for Bulletin 284E ArmorStart.
204
Option not valid for Bulletin 284E ArmorStart.
205
Comm Loss Action
Selects the drive’s response to a loss of the communication
connection or excessive communication errors.
0 = Fault
Drive Advanced Setup
206
Comm Loss Time
Sets the time that the drive remain in communication loss before
implanting the option selected in Parameter 205 (Comm Loss
Action).
15.0 Secs
Drive Advanced Setup
207
Option not valid for Bulletin 284E ArmorStart.
208
Option not valid for Bulletin 284E ArmorStart.
209
Option not valid for Bulletin 284E ArmorStart.
210
Option not valid for Bulletin 284E ArmorStart.
211
Option not valid for Bulletin 284E ArmorStart.
212
Option not valid for Bulletin 284E ArmorStart.
213
Option not valid for Bulletin 284E ArmorStart.
214
Slip Hertz @ FLA
Compensates for the inherent slip in an induction motor. This
frequency is added to the commanded output frequency based
on motor current.
2.0 Hz
Drive Advanced Setup
Table 29 - Parameter Descriptions
Parameter
Number
Parameter
Name
Description
Factory Default
Group