Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 248

Advertising
background image

248

Rockwell Automation Publication 280E-UM001B-EN-P - July 2012

Chapter 11 Specifications for EtherNet/IP

➊ Add power requirements for outputs (1 A max.) to A1/A2.
➋ Add power requirements for inputs (200 mA max.) to A3/A2.
➌ If A1 power is disconnected.

Other Rating

EMC Emission Levels

Conducted Radio Frequency Emissions

10V rms Communications Cables

10V rms (PE)

150 kHz…80 MHz

Radiated Emissions

Class A

EMC Immunity Levels

Electrostatic Discharge

4 kV contact and 8 kV Air

Radio Frequency Electromagnetic Field

10V/m, 80 KHz…1 GHz

3V/m, 1.4 GHz…2 GHz

1V/m, 2.0 GHz …2.7 GHz

Fast Transient

2 kV (Power)

2 kV (PE)

1 kV (Communications and Control)

Surge Transient

1 kV (12) L-L, 2 kV (2) L-N (Earth)

UL/NEMA

IEC

UL/NEMA

IEC

Standards Compliance

UL 508C

CSA C22.2, No. 14

EN50178

EN61800-3

EN/IEC 60947-4-2

CE Marked per Low Voltage 2006/95/EC

EMC Directive 2004/108/EC

CCC

ODVA for EtherNet/IP

Certifications

cULus (File No. E207834,

Guide NMMS, NMMS7)

EtherNet/IP Version – Control and I/O Power Requirements

Units A1/A2

A3/A2

A3/A2

Control Voltage

Volts

24V DC

Current

Amps 0.375

0.125

0.35

Total Control Power (no options)

Watts

9

3

8.4

Total Control Power (with Dynamic Brake or Output Contactor option)

Watts

12

3

8.4

Total Control Power (with Dynamic Brake and Output Contactor option)

Watts

15

3

8.4

Drive Characteristics

Sensorless Vector Control

Maximum (kW) Hp Rating/Input Voltage

5 Hp (3.3 kW)/480V AC

Overload Capacity

150% for 60 s

200% for 3 s

Preset Speeds

8

Carrier Frequency

2…16 kHz