Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 248

248
Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 11 Specifications for EtherNet/IP
➊ Add power requirements for outputs (1 A max.) to A1/A2.
➋ Add power requirements for inputs (200 mA max.) to A3/A2.
➌ If A1 power is disconnected.
Other Rating
EMC Emission Levels
Conducted Radio Frequency Emissions
10V rms Communications Cables
10V rms (PE)
150 kHz…80 MHz
Radiated Emissions
Class A
EMC Immunity Levels
Electrostatic Discharge
4 kV contact and 8 kV Air
Radio Frequency Electromagnetic Field
10V/m, 80 KHz…1 GHz
3V/m, 1.4 GHz…2 GHz
1V/m, 2.0 GHz …2.7 GHz
Fast Transient
2 kV (Power)
2 kV (PE)
1 kV (Communications and Control)
Surge Transient
1 kV (12) L-L, 2 kV (2) L-N (Earth)
UL/NEMA
IEC
UL/NEMA
IEC
Standards Compliance
UL 508C
CSA C22.2, No. 14
EN50178
EN61800-3
EN/IEC 60947-4-2
CE Marked per Low Voltage 2006/95/EC
EMC Directive 2004/108/EC
CCC
ODVA for EtherNet/IP
Certifications
cULus (File No. E207834,
Guide NMMS, NMMS7)
EtherNet/IP Version – Control and I/O Power Requirements
Units A1/A2
➊
A3/A2
➋
A3/A2
➌
Control Voltage
Volts
24V DC
Current
Amps 0.375
0.125
0.35
Total Control Power (no options)
Watts
9
3
8.4
Total Control Power (with Dynamic Brake or Output Contactor option)
Watts
12
3
8.4
Total Control Power (with Dynamic Brake and Output Contactor option)
Watts
15
3
8.4
Drive Characteristics
Sensorless Vector Control
Maximum (kW) Hp Rating/Input Voltage
5 Hp (3.3 kW)/480V AC
Overload Capacity
150% for 60 s
200% for 3 s
Preset Speeds
8
Carrier Frequency
2…16 kHz