Starter setup group (bulletin 280e/281e only) – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 132

Advertising
background image

132

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Starter Setup Group (Bulletin 280E/281E only)

FLA Setting

The motor’s full load current rating is
programmed in this parameter.

Parameter Number

106

Access Rule

GET/SET

Data Type

INT

Group

Starter Setup

Units

xx.x Amps

Minimum Value

See Table 19.

Maximum Value

See Table 19.

Default Value

See Table 19.

Table 19 - FLA Setting Ranges and Default Values (with indicated setting precision)

FLA Current Range (A)

Default Value

Minimum Value

Maximum Value

0.24

1.2

0.24

0.5

2.5

0.5

1.1

5.5

1.1

3.2

16.0

3.2

Overload Class

This parameter allows the installer to
select the overload class.
1 = Overload Class 10
2 = Overload Class 15
3 = Overload Class 20

Parameter Number

107

Access Rule

GET/SET

Data Type

USINT

Group

Starter Setup

Units

xx.x Amps

Minimum Value

1

Maximum Value

3

Default Value

1

OL Reset Level

This parameter allows the installer
select the % Thermal Capacity which
an overload can be cleared.

Parameter Number

108

Access Rule

GET/SET

Data Type

USINT

Group

Starter Setup

Units

% FLA

Minimum Value

0

Maximum Value

100

Default Value

75

Advertising