Overload object, Class code 0x002c – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 295

Advertising
background image

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

295

CIP Information Appendix B

➊ Reversing Starters and Inverter Starters only.

Inverter Starters only

The following common services are implemented for the Control Supervisor
Object.

Overload Object

CLASS CODE 0x002C

No class attributes will be supported for the Overload Object.

A single instance (Instance 1) of the Overload Object is supported for DOL and
Reversing Starters. Instance 1 contains the following instance attributes.

154

Get

Starter Enclosure

WORD

Bit 0 = IP67
Bit 1 = NEMA 4x
Bits 2…15 Reserved

155

Get

Starter Options

WORD

Bit 0 = Full Keypad
Bit 1 = Safety Monitor
Bit 2 = Source Brake
Bit 3 = CP Brake
Bit 4 = Dynamic Brake
Bit 5 = Output Contactor
Bit 6 = EMI Filter
Bit 7 = 0…10V Analog In
Bits 8…15 = Reserved

156

Get

Last Pr Trip

UINT

157

Get

DB Status

WORD

Bit 0 = DB Faulted
Bit 1 = DB Overtemp Warning
Bit 2 = DB On
Bit 3 = DB Flt Reset Inhibit
Bits 4…15 = Reserved

158

Get

DB Fault

WORD

Bit 0 = DB Overtemp
Bit 1 = DB OverCurrent
Bit 2 = DB UnderCurrent
Bit 3 = DB Shorted Switch
Bit 4 = DB Open
Bit 5 = Reserved
Bit 6 = DB Bus Voltage Link Open
Bit 7 = Reserved
Bit 8 = DB Comms
Bits 9…15 = Reserved

Attribute ID

Access Rule

Name

Data Type

Value

Service Code

Implemented for:

Service Name

Class Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single