Ethernet/ip led status indication – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 211

Advertising
background image

Rockwell Automation Publication 280E-UM001B-EN-P - July 2012

211

Diagnostics Chapter 9

EtherNet/IP LED Status
Indication

EtherNet/IP LED status and diagnostics consists of four LEDs.

• Link Activity/Status LEDS

– Link1 Activity/Status (Port 1) – LED Color: Bicolor (Green/Yellow).

refer to Table 31

– Link2 Activity/Status (Port 2) – LED Color: Bicolor (Green/Yellow).

refer to Table 31

• “MOD” LED – Bicolor Red/Green represents the Ethernet Module

status, refer to Table 32

• “NET” LED – Bicolor Red/Green represents the Ethernet Network

status, refer to Table 34

Refer to Parameter 63 “Base Trip” for the Base Module Trip Status.

Figure 80 - EtherNet/IP LED

Table 31 - Link 1 or Link 2 Port Activity/Status

Link 1 or 2 Status LED

Description

Recommended Action

OFF

No link established

Verify network cabling, and correct, as needed.

Green

Link established at 100 Mbps

None

Flashing green

Transmit or receive activity present at 100 Mbps

None

Yellow

Link established at 10 Mbps

None

Flashing yellow

Transmit or receive activity present at 10 Mbps

None

Table 32 - Module Status Indicator

MOD Status LED

Summary

Requirement

Steady OFF

No power

If no power is supplied to the device, the module status indicator shall be steady OFF.

Steady Green

Device operational

If the device is operating correctly, the module status indicator shall be steady green.

Flashing Green

Standby

If the device has not been configured, the module status indicator shall be flashing
green.

Flashing Red

Minor fault

If the device has detected a recoverable minor fault, the module status indicator shall
be flashing red.
Note: An incorrect or inconsistent configuration would be considered a minor fault.

Steady Red

Major fault

If the device has detected a non-recoverable major fault, refer to Table 33.

Flashing Green/Red

Self-test

While the device is performing its power up testing, the module status indicator shall
be flashing green/red.

Advertising