Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

167

Bulletin 280E/281E/284E Programmable Parameters Chapter 7

Relay Out Level

Sets the trip point for the digital output relay if the value of Parameter
155 (Relay Out Sel) is 6, 7, 8, 10, 16, 17, 18, or 20.

Parameter Number

156

Related Parameters

155

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1

Minimum Value

0.0

Maximum Value

9999

Default Value

0.0

Parameters 155 Setting

Parameter 156 Min./Max.

6

0/400 Hz

7

0/180%

8

0/815V

10

0/100%

16

0.1/9999 sec

17

1/9999 counts

18

1/180

°

20

0/1

Accel Time 2

When active, sets the rate of acceleration for all speed increases except for jog.

Parameter Number

167

Related Parameters

139, 151…154, 170…177,

240…247

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 sec

Minimum Value

0.0

Maximum Value

600.0

Default Value

20.0

Maximum Freq

Accel Time

--------------------------------------

Accel Rate

=

Parameter 135
(Maximum Freq)

Speed

Param.
139 or
167
(Accel
Time x)

0

0

Time

Param.
140 or
168
(Decel
Time x)

Ac

celer

ation

Dec

eler

ation

Decel Time 2

When active, sets the rate of deceleration for all speed decreases except for jog.

Parameter Number

168

Related Parameters

140, 151…154, 170…177,

240…247

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 sec

Minimum Value

0.0

Maximum Value

600.0

Default Value

20.0

Maximum Freq

Decel Time

--------------------------------------

Decel Rate

=

Parameter 135
(Maximum Freq)

Speed

Param.
139 or
167
(Accel
Time x)

0

0

Time

Param.
140 or
168
(Decel
Time x)

Ac

celer

ation

Dec

eler

ation