Drive I/O Configuration Group (Bulletin 284E only)

Drive Control

This parameter provides the status of
drive parameters.

Parameter Number

48

Access Rule

GET

Data Type

WORD

Group

Drive I/O Config.

Units

Minimum Value

0

Maximum Value

4095

Default Value

0

Bit

Function

11

10

9

8

7

6

5

4

3

2

1

0

X

Accel 1 En

X

Accel 2 En

X

Decel 1 En

X

Decel 2 En

X

Freq Sel 0

X

Freq Sel 1

X

Freq Sel 2

X

Reserved

X

Drv In 1

X

Drv In 2

X

Drv In 3

X

Drv In 4

DrvIn Pr FltState

This parameter, in conjunction with
Parameter 50 (DrvIn Pr FltValue),
defines how the Drive Digital
Inputs 1…4 will respond when a
protection trip occurs. When set to “1”,
Drive Digital Inputs 1…4 continue to
operate as command via the network.
When set to “0”, Drive Digital Inputs
1…4 will open or close as
determined by setting in Parameter
50.
0 = Go to PrFlt Value
1 = Ignore PrFlt

Parameter Number

49

Access Rule

GET/SET

Data Type

BOOL

Group

Drive I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0