CIP Information Appendix B
All instances contain the following attributes.
➊ For DOP Instances 1, 2, 9 and 10, Attributes 113 and 114 have “Get” only access, and their values are always 0.
The following common services are implemented for the Discrete Output Point
Object.
Instance Name
Alternate
Mapping
Description
1
Run Fwd Output
0029-01-03
Run Forward output. For all starter types, this output is hard wired from the
ArmorStart CPU to the actuator.
2
Run Rev Output
0029-01-04
Run Reverse output. For all starter types, this output is hard wired from the
ArmorStart CPU to the actuator.
3
User Output 1
None
These are the two ArmorStart user outputs for all starter types.
4
User Output 2
None
5
Drive Input 1
None
These four instances exist for Inverter units only. They are drive the outputs on
the main control board that are connected to Drive Inputs 1…4.
6
Drive Input 2
None
7
Drive Input 3
None
8
Drive Input 4
None
9
Drive Jog Fwd
None
This instances exists for Inverter units only.
10
Drive Jog Rev
None
Attribute ID
Access Rule
Name
Data Type
Value
3
Get
Value
BOOL
0 = OFF, 1 = ON
5
Get/Set
Fault Action
BOOL
0 = Fault Value attribute, 1 = Hold Last State
6
Get/Set
Fault Value
BOOL
0 = OFF, 1 = ON
7
Get/Set
Idle Action
BOOL
0 = Fault Value attribute, 1 = Hold Last State
8
Get/Set
Idle Value
BOOL
0 = OFF, 1 = ON
113
Get/Set
➊
Pr Fault Action
BOOL
0 = Pr Fault Value attribute, 1 = Ignore
114
Get/Set
➊
Pr Fault Value
BOOL
0 = OFF, 1 = ON
115
Get/Set
Force Enable
BOOL
0 = Disable, 1 = Enable
116
Get/Set
Force Value
BOOL
0 = OFF, 1 = ON
117
Get/Set
Input Binding
STRUCT:
USINT
Array of USINT
Size of Appendix I encoded path
Appendix I encoded path
NULL path means Attribute 3 drives the output.
Otherwise, this is a path to a bit in the Bit Table.
Service Code
Implemented for:
Service Name
Class Instance
0x0E Yes
Yes
Get_Attribute_Single
0x10 No
Yes
Set_Attribute_Single