Rockwell Automation Publication 280E-UM001B-EN-P - July 2012

261

Accessories Chapter 12

Recommended thermostat control wiring to prevent dynamic brake overheating.

Figure 93 - Thermostat Control Wiring

Sensorless Vector Control (SVC) Recommended Dynamic Brake
Modules for Option DB1 (IP67 Resistor)

Drive rating and DB part numbers are not interchangeable. Only use specified resistor. Customer is responsible to evaluate if

performance meets application requirement.

Note:

Duty Cycle listed is based on full speed to zero speed deceleration. For

constant regen at full speed, duty cycle capability is half of what is listed.

Application Type 1 represents maximum capability up to 100% braking torque
where possible.

3-Phase
Power

R (L1)

S (L2)

T (L3)

(M)
Contactor

Power On

Power Source

DB Resistor Thermostat

Power Off

M

M

Drive and

Motor Size

kW

Cat. No.

Resistance

Ohms ± 5%

Continuous

Power kW

Max Energy

kJ

Max Braking

Torque % of

Motor

Application Type 1

Application Type 2

Braking

Torque % of

Motor

Duty

Cycle %

Braking

Torque % of

Motor

Duty

Cycle %

380…480 Volt AC Input Drives

0.37 (0.5)

284R-360P500-M*

360

0.086

17

305%

100%

47%

150%

31%

0.75 (1)

284R-360P500-M*

360

0.086

17

220%

100%

23%

150%

15%

1.5 (2)

284R-360P500-M*

360

0.086

17

110%

100%

12%

110%

11%

2.2 (3)

284R-120P1K2-M*

120

0.26

52

197%

100%

24%

150%

16%

4 (5)

284R-120P1K2-M*

120

0.26

52

124%

100%

13%

124%

10%