Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Drive Display Group (Bulletin 284E only)

DrvIn Net IdlValue

This parameter determines the state
that Drive Digital Inputs 1…4 assume
when the network is idle and
Parameter 53 (DrvIn Net IdlState) is
set to “0”.
0 = OFF
1 = ON

Parameter Number

54

Access Rule

GET/SET

Data Type

BOOL

Group

Drive I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

High Speed Enable

Enable High Speed Inverter control
thru the terminal block.
0 = Disabled
1 = Enabled

Parameter Number

55

Access Rule

GET/SET

Data Type

BOOL

Group

Drive I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Output Freq

Output frequency present at T1, T2,
T3.

Parameter Number

101

Related Parameters

102, 110, 134, 135, 138

Access Rule

GET

Data Type

UINT

Group

Drive Display

Units

0.1 Hz

Minimum Value

0.0

Maximum Value

400.0 Hz

Default Value

Read Only

Commanded Freq

Value of the active frequency
command. Displays the commanded
frequency even if the drive is not
running.

Parameter Number

102

Related Parameters

101, 113, 134, 135, 138

Access Rule

GET

Data Type

UINT

Group

Drive Display

Units

0.1 Hz

Minimum Value

0.0

Maximum Value

400.0 Hz

Default Value

Read Only