Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

OutA Pr FltValue

This parameter determines the state
the Output A assumes when a trip
occurs and Parameter 33 (OutA Pr
FltState) is set to “0”.
0 = Open
1 = Close

Parameter Number

34

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Net FltState

This parameter in conjunction with
Parameter 36 (OutA Net FltValue)
defines how Output A will respond
when a network fault occurs.
0 = Goto Net FltValue
1 = Hold Last State
When set to “1”, Output A will hold
state prior to trip occurrence. When set
to “0”, Output A will open or close as
determined by the setting in
Parameter 36.

Parameter Number

35

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Net FltValue

This parameter determines the state
that Output A assumes when a
network fault occurs and Parameter
35 (OutA Net FltState) is set to “0”.
0 = Open
1 = Close

Parameter Number

36

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Net IdlState

This parameter in conjunction with
Parameter 38 (OutA Net IdlValue)
defines how Output A will respond
when the network is idle.
0 = Goto Net IdlValue
1 = Hold Last State
When set to “0”, Output A will open or
close as determined by the setting in
Parameter 38.

Parameter Number

37

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0