A3 Power Loss

Power has been lost or has dropped below the 12V threshold

.

This fault can be

disabled and

is disabled by default.

Internal Communication Fault

Indicates an internal communication fault has been detected. This fault cannot
be disabled.

DC Bus Fault

Indicates the drive has detected a DC Bus Fault. This fault cannot be disabled.

Electrically Erasable Programmable Read-Only Memory
EEPROM Fault

This is a major fault, which renders the ArmorStart inoperable. This fault cannot
be disabled.

Hardware Fault

Indicates incorrect base/starter assembly or other hardware fault. This fault
cannot be disabled.

Restart Retries

This fault is generated when the drive detects that the auto retries count has been
exceeded. This fault cannot be disabled.

Miscellaneous Faults

• For Bulletin 284E units, this fault is actually the logical of several drive

faults not specifically enumerated.

• This fault cannot be disabled.