Bulletin 280E/281E/284E Programmable Parameters Chapter 7

Bus Reg Mode

Enables the bus regulator.
0 = Disable
1 = Enabled

Parameter Number

217

Related Parameters

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

1

Default Value

1

Current Limit 2

Maximum output current allowed
before current limiting occurs. This
parameter is only active if Parameters
151…154 (Digital In x Sel) is set to
Option 25 (Current Lmt2) and is
active.

Parameter Number

218

Related Parameters

133, 151…154, 189

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 A

Minimum Value

0.0 A

Maximum Value

Drive rated amps x 1.8

Default Value

Drive rated amps x 1.5

Skip Frequency

Sets the frequency at which the drive
will not operate.

Parameter Number

219

Related Parameters

220

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 Hz

Minimum Value

0.0

Maximum Value

400.0 Hz

Default Value

0.0 Hz

Skip Freq Band

Determines the band width around
Parameter 219 (Skip Frequency).
Parameter 220 (Skip Freq Band) is
split applying 1/2 above and 1/2
below the actual skip frequency. A
setting of 0.0 disables this parameter.

Parameter Number

220

Related Parameters

219

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 Hz

Minimum Value

0.0 Hz

Maximum Value

30.0 Hz

Default Value

0.0 Hz