Bulletin 280E/281E/284E Programmable Parameters Chapter 7

EM Brk On Delay

Sets the time the drive will remain at
minimum frequency before stopping
and de-energizing the brake coil relay
when Parameter 137 (Stop Mode) is
set to Option 8 or 9.

Parameter Number

261

Related Parameters

134, 137

Access Rule

GET/SET

Data Type

UNIT

Group

Drive Advanced Setup

Units

0.01 sec

Minimum Value

0.01 sec

Maximum Value

10.00 sec

Default Value

0.0 sec

MOP Reset Sel

Sets the drive to save the current MOP
Reference command.
0 = Zero MOP Ref
This option clamps Parameter 169
(Internal Freq) at 0.0 Hz when drive is
not running.
1 = Save MOP Ref (Default)
Reference is saved in Parameter 169
(Internal Freq).

Parameter Number

262

Related Parameters

169

Access Rule

Get/Set

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

1

Default Value

1

DB Threshold

Sets the DC bus Voltage Threshold for
Dynamic Brake operation. If the DC
bus voltage falls below the value set
in this parameter, the Dynamic Brake
will not turn on. Lower values will
make the Dynamic Braking function
more responsive, but may result in
nuisance Dynamic Brake activation.

Parameter Number

263

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0.0%

Maximum Value

110.0%

Default Value

100%

ATTENTION: Equipment damage may result if this parameter is set to a value that
causes the dynamic braking resistor to dissipate excessive power. Parameter settings
less than 100% should be carefully evaluated to ensure that the dynamic brake
resistor’s wattage rating is not exceeded. In general, values less than 90% are not
needed. This parameter’s setting is especially important if Parameter 182 (DB Resistor
Sel) is set to “2” (No Protection).