190

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Figure 74 - EM Brk OFF Delay

StpLogic Time 0 (250)
StpLogic Time 1 (251)
StpLogic Time 2 (252)
StpLogic Time 3 (253)
StpLogic Time 4 (254)
StpLogic Time 5 (255)
StpLogic Time 6 (256)
StpLogic Time 7 (257)

Sets the time to remain in each step if
the corresponding Parameter 138
(Speed Reference) is set to “6”
(StpLogic), Parameter 240-247
(StpLogic x), digits 0…3 set to b, C, d
or E (Step after (StpLogic Time x).

Parameter Number

250…257

Related Parameters

138, 155, 171…177, 240…247

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 sec

Minimum Value

0.0 sec

Maximum Value

999.9 sec

Default Value

30.0 sec

EM Brk OFF Delay

Sets the time the drive will remain at
minimum frequency before ramping
to the commanded frequency and
energizing the brake coil relay when
Parameter 137 (Stop Mode) is set to
Option 8 or 9.

Parameter Number

260

Related Parameters

134, 137

Access Rule

GET/SET

Data Type

UNIT

Group

Drive Advanced Setup

Units

0.01 sec

Minimum Value

0.01 sec

Maximum Value

10 sec

Default Value

0.0 sec

Frequency

Time

Minimum Freq

260 [EM Brk Off Delay]

261 [EM Brk On Delay]

Stop

Commanded

Start

Commanded

EM Brk

De-Energized (On)

Drive Stops

EM Brk
Energized (Off)

Ramp A

cc

el

Ramp D

ecel