User I/O Configuration Group

Anti-bounce On Delay

This parameter allows the installer to
program a time duration before being
reported “ON” (Anti-bouce).

Parameter Number

30

Access Rule

GET/SET

Data Type

UINT

Group

User I/O Config.

Units

ms

Minimum Value

0

Maximum Value

65

Default Value

0

Anti-bounce OFF Delay

This parameter allows the installer to
program a time duration before being
reported “OFF” (Anti-bouce).

Parameter Number

31

Access Rule

GET/SET

Data Type

UINT

Group

User I/O Config.

Units

ms

Minimum Value

0

Maximum Value

65

Default Value

0

In Sink/Source

This parameter allows the installer to
program the inputs to be sink or
source.
0 = Sink
1 = Source

Parameter Number

32

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Pr FltState

This parameter in conjunction with
Parameter 34 (OutA Pr FltValue)
defines how Output A will respond
when a trip occurs.
0 = Goto PrFlt Value
1 = Ignore PrFlt
When set to “1”, Output A continues to
operate as command via the network.
When set to “0”, Output A will open or
close as determined by the setting in
Parameter 34.

Parameter Number

33

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0