Connection Manager Object
CLASS CODE 0x0006
The following class attributes will be supported for the Connection Manager
Object.
Two Class 1 connections for I/O transfer will be supported.
Six Class 3 explicit connections will be supported.
The following instance attributes will be supported:
Instance 166 Consumed Inverter Type Starter with Network Inputs
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Out B
Out A
—
JogReverse
JogForward
ResetFault
RunReverse
RunForward
1 DriveInput4
DriveInput3
DriveInput2
DriveInput1
DecelCtrl_1
DecelCtrl_0
AccelCtrl_1
AccelCtrl_0
2
FreqCommand (Low) (xxx.x Hz)
3
FreqCommand (High) (xxx.x Hz)
4
Pt07DeviceIn
Pt06DeviceIn
Pt05DeviceIn
Pt04DeviceIn
Pt03DeviceIn
Pt02DeviceIn
Pt01DeviceIn
Pt00DeviceIn
5
Pt15DeviceIn
Pt14DeviceIn
Pt13DeviceIn
Pt12DeviceIn
Pt11DeviceIn
Pt10DeviceIn
Pt9DeviceIn
Pt8DeviceIn
Attribute ID
Access Rule
Name
Data Type
Value
1 Get
Revision
UINT
1
2 Get
Max
Instance
UINT
—
3
Get
Number of Instances
UINT
—
4
Get
Optional Attribute List
Array of UINT
—
6
Get
Max Number Class Attribs
UINT
—
Attribute ID
Access Rule
Name
Data Type
Value
1
Get/Set
Open Requests
UINT
Number of Forward Open service requests received.
2
Get/Set
Open Format Rejects
UINT
Number of Forward Open service requests which were
rejected due to bad format.
3
Get/Set
Open Resource Rejects
UINT
Number of Forward Open service requests which were
rejected due to lack of resources.
4
Get/Set
Open Other Rejects
UINT
Number of Forward Open service requests which were
rejected for reasons other than bad format or lack of
resources.
5
Get/Set
Close Requests
UINT
Number of Forward Close service requests received.
6 Get/Set Close
Format
Requests
UINT
Number of Forward Close service requests which were
rejected due to bad format.
7 Get/Set Close
Other
Requests
UINT
Number of Forward Close service requests which were
rejected for reasons other than bad format.
8 Get/Set Connection
Timeouts
UINT
Total number of connection timeouts that have occurred in
connections controlled by this Connection Manager