Fault definitions, Short circuit, Overload trip – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 208: Phase loss, Short circuit overload trip phase loss, Table 30 pr

Advertising
background image

208

Rockwell Automation Publication 280E-UM001B-EN-P - July 2012

Chapter 9 Diagnostics

Table 30 - Fault Indication

Fault Definitions

Short Circuit

Short Circuit indicates that the Bulletin 140M motor protector has tripped, or
that the internal wiring protection algorithm has detected an unsafe current
surge. This fault cannot be disabled.

Overload Trip

The load has drawn excessive current and based on the overload trip class
selected, the device has tripped. This fault cannot be disabled.

Phase Loss

Indicates a missing supply phase. This fault can be disabled and is disabled by
default.

Blink Pattern

Fault Types

Bulletin 280E/281E

Bulletin 284E

1

Short Circuit

Short Circuit

2

Overload Trip

Overload Trip

3

Phase Loss

Phase Short

4

Reserved

Ground Fault

5

Reserved

Stall

6

Control Power

Control Power

7

I/O Fault

I/O Fault

8

Over Temperature

Over Temperature

9

Phase Imbalance

Over Current

10

A3 Power Loss

A3 Power Loss

11

Reserved

Internal Communications

12

Reserved

DC Bus Fault

13

EEPROM Fault

EEPROM Fault

14

Hardware Fault

Hardware Fault

15

Reserved

Restart Retries

16

Reserved

Misc. Fault