Fault definitions, Short circuit, Overload trip – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 208: Phase loss, Short circuit overload trip phase loss, Table 30 pr

208
Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 9 Diagnostics
Table 30 - Fault Indication
Fault Definitions
Short Circuit
Short Circuit indicates that the Bulletin 140M motor protector has tripped, or
that the internal wiring protection algorithm has detected an unsafe current
surge. This fault cannot be disabled.
Overload Trip
The load has drawn excessive current and based on the overload trip class
selected, the device has tripped. This fault cannot be disabled.
Phase Loss
Indicates a missing supply phase. This fault can be disabled and is disabled by
default.
Blink Pattern
Fault Types
Bulletin 280E/281E
Bulletin 284E
1
Short Circuit
Short Circuit
2
Overload Trip
Overload Trip
3
Phase Loss
Phase Short
4
Reserved
Ground Fault
5
Reserved
Stall
6
Control Power
Control Power
7
I/O Fault
I/O Fault
8
Over Temperature
Over Temperature
9
Phase Imbalance
Over Current
10
A3 Power Loss
A3 Power Loss
11
Reserved
Internal Communications
12
Reserved
DC Bus Fault
13
EEPROM Fault
EEPROM Fault
14
Hardware Fault
Hardware Fault
15
Reserved
Restart Retries
16
Reserved
Misc. Fault