Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

171

Bulletin 280E/281E/284E Programmable Parameters Chapter 7

Figure 68 - S Curve

S Curve %

Sets the percentage of acceleration or
deceleration time that is applied to
ramp as S Curve. Time is added, half at
the beginning and half at the end of
the ramp.

Parameter Number

183

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

1%

Minimum Value

0

Maximum Value

100

Default Value

0% disabled

Example:
Accel Time = 10 Seconds
S Curve Setting = 50%
S Curve Time = 10 x 0.5 = 5 Seconds
Total Time = 10 + 5 = 15 Seconds

1/2 S Curve Time

2.5 Seconds

Total Time to Accelerate = Accel Time + S Curve Time

Accel Time

10 Seconds

50% S Curve

Target 2

Target

1/2 S Curve Time

2.5 Seconds

Boost Select

Sets the boost voltage (% of
Parameter 131 (Motor NP Volts)) and
redefines the Volts per Hz curve.
Active when Parameter 225 (Torque
Perf Mode) = 0 (V/Hz). Drive may add
additional voltage unless Option 5 is
selected.

See Table 23 for details.

Parameter Number

184

Related Parameters

104, 131, 132, 185…187, 225

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

14

Default Value

8

Table 23 - Boost Select Options

Options

Description

0

Custom V/Hz

Variable Torque

(Typical fan/pump curves)

1

30.0, VT

2

35.0, VT

3

40.0, VT

4

45.0, VT