Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

161

Bulletin 280E/281E/284E Programmable Parameters Chapter 7

Motor NP Hertz

Set to the motor nameplate rated
frequency.

Parameter Number

132

Related Parameters

184, 185…187, and 190

Access Rule

GET/SET

Data Type

UINT

Group

Drive Setup

Units

1 Hz

Minimum Value

15

Maximum Value

400

Default Value

60 Hz

Motor OL Current

Set to the maximum allowable
current. The drive fault on an F7
Motor Over load if the value of this
parameter is exceeded by 150%
for 60 s.

Parameter Number

133

Related Parameter

155, 189, 190, 198, 214, 218,

260…261

Access Rule

GET/SET

Data Type

UINT

Group

Drive Setup

Units

0.1 A

Minimum Value

0.0

Maximum Value

Drive rated amps x 2

Default Value

Based on Drive Rating

Minimum Freq

Sets the lowest frequency the drive
will output continuously.

Parameter Number

134

Related Parameter

101, 102, 113, 135, 185…187,

260, 261

Access Rule

GET/SET

Data Type

UINT

Group

Drive Setup

Units

0.1 Hz

Minimum Value

0.0

Maximum Value

400

Default Value

0.0

Stop drive before changing this
parameter.

O