Bulletin 280E/281E/284E Programmable Parameters Chapter 7

OutA Net FltState

This parameter in conjunction with
Parameter 36 (OutA Net FltValue)
defines how Output A will respond
when a network fault occurs.
0 = Goto Net FltValue
1 = Hold Last State
When set to “1”, Output A will hold
state prior to trip occurrence. When set
to “0”, Output A will open or close as
determined by setting in Parameter
36.

Parameter Number

35

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Net FltValue

This parameter determines the state
that Output A assumes when a
network fault occurs and Parameter
35 (OutA Net FltState) is set to “0”.
0 = Open
1 = Close

Parameter Number

36

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Net IdlState

This parameter in conjunction with
Parameter 38 (OutA Net IdlValue)
defines how Output A will respond
when the network is idle.
0 = Goto Net IdlValue
1 = Hold Last State
When set to “0”, Output A will open or
close as determined by the setting in
Parameter 38.

Parameter Number

37

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Net IdlValue

This parameter determines the state
that Output A assumes when the
network is idle and Parameter 37
(OutA Net IdlState) is set to “0”.
0 = Open
1 = Close

Parameter Number

38

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0