Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Relay Out Sel

Sets the condition that changes the
state of the output relay contacts.

Parameter Number

155

Related Parameters

133, 156, 192, 240…247,

250…257, 260, 261

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

22

Default Value

22

Table 21 - Options for the Output Relay Contacts

Options

Name

Description

0

Ready/Fault (Default)

Relay changes state when power is applied. This indicates the drive is ready for operation. Relay returns drive to shelf state when power is
removed or a fault occurs.

1

At Frequency

Drive reached commanded frequency.

2

MotorRunning

Motor is receiving power from drive.

3

Reverse

Drive is commanded to run in reverse direction.

4

Motor Overld

Motor overload condition exists.

5

Ramp Reg

Ramp regulator is modifying the programmed accel/decal times to avoid overcurrent or overvoltage fault from occurring.

6

Above Freq

Drive exceeds the frequency (Hz) value set in Parameter 156 (Relay Out Level) Use Parameter 156 to set threshold.

7

Above Cur

Drive exceeds the current (% Amps) value set in Parameter 156 (Relay Out Level) Use Parameter 156 to set threshold.

8

Above DCVolt

Drive exceeds the DC bus voltage value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.

9

Retries Exst

Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.

10

Above Anlg V

Option not valid for Bulletin 284E ArmorStart.

11

Logic In 1

An input is programmed as Logic In 1 and is active.

12

Logic In 2

An input is programmed as Logic In 2 and is active.

13

Logic In 1 & 2

Both Logic inputs are programmed and active.

14

Logic In 1 or 2

One or both Logic inputs are programmed and one or both is active.

15

StpLogic Out

Drive enters StepLogic step with Digit 3 of Command Word (Parameters 240…247).

16

Timer Out

Timer has reached value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.

17

Counter Out

Counter has reached value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.

18

Above PF Ang

Power factor angle has exceeded the value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.

19

Anlg In Loss

Option not valid for Bulletin 284E ArmorStart.

20

ParamControl

Enables the output to be controlled over the network communications by writing to Parameter 156 (Relay Out Level) (0 = OFF, 1 = ON).

21

NonRec Fault

Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.

22

EM Brk Cntrl

EM Brake is energized. Program Parameter 260 (EM Brk OFF Delay) and Parameter 261 (EM Brk On Delay) for desired action.

23

Above Fcmd

The Current Command Frequency exceeds the value set in Parameter 156 (Relay Out Level).

24

Msg Control

With Drive FRN4.01 or later, this option enables the output to be controlled over the network communication.