Control supervisor object, Class code 0x0029 – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 293

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
293
CIP Information Appendix B
Instance 2 contains the following instance attributes.
The following common services are implemented for the Discrete Output Group
Object.
Control Supervisor Object
CLASS CODE 0x0029
No class attributes are supported.
A single instance (Instance 1) of the Control Supervisor Object is supported and
contains the following instance attributes.
Attribute ID
Access Rule
Name
Data Type
Value
3
Get
Number of Instances
USINT
4
4
Get
Binding
Array of UINT
5, 6, 7, 8
7
Get/Set
Fault Action
BOOL
0 = Fault Value Attribute, 1 = Hold Last State
8
Get/Set
Fault Value
BOOL
0 = OFF, 1 = On
9
Get/Set
Idle Action
BOOL
0 = Idle Value Attribute, 1 = Hold Last State
10
Get/Set
Idle Value
BOOL
0 = OFF, 1 = On
113
Get/Set
Pr Fault Action
BOOL
0 = Pr Fault Value Attribute, 1 = Ignore
114
Get/Set
Pr Fault Value
BOOL
0 = OFF, 1 = On
Service Code
Implemented for:
Service Name
Class Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Attribute ID
Access Rule
Name
Data Type
Value
3
Get/Set
Run 1
BOOL
These Run outputs also map to DOP
Instances 1 and 2
4
➊
Get/Set
Run 2
BOOL
—
7
Get
Running 1
BOOL
—
8
➊
Get
Running 2
BOOL
—
9
Get
Ready
BOOL
—
10
Get
Tripped
BOOL
—
12
Get/Set
Fault Reset
BOOL
0->1 = Trip Reset
100
Get/Set
Keypad Mode
BOOL
0 = Maintained, 1 = Momentary
101
Get/Set
Keypad Disable
BOOL
0 = Not Disabled, 1= Disabled