Control supervisor object, Class code 0x0029 – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 293

Advertising
background image

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

293

CIP Information Appendix B

Instance 2 contains the following instance attributes.

The following common services are implemented for the Discrete Output Group
Object.

Control Supervisor Object

CLASS CODE 0x0029

No class attributes are supported.

A single instance (Instance 1) of the Control Supervisor Object is supported and
contains the following instance attributes.

Attribute ID

Access Rule

Name

Data Type

Value

3

Get

Number of Instances

USINT

4

4

Get

Binding

Array of UINT

5, 6, 7, 8

7

Get/Set

Fault Action

BOOL

0 = Fault Value Attribute, 1 = Hold Last State

8

Get/Set

Fault Value

BOOL

0 = OFF, 1 = On

9

Get/Set

Idle Action

BOOL

0 = Idle Value Attribute, 1 = Hold Last State

10

Get/Set

Idle Value

BOOL

0 = OFF, 1 = On

113

Get/Set

Pr Fault Action

BOOL

0 = Pr Fault Value Attribute, 1 = Ignore

114

Get/Set

Pr Fault Value

BOOL

0 = OFF, 1 = On

Service Code

Implemented for:

Service Name

Class Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Attribute ID

Access Rule

Name

Data Type

Value

3

Get/Set

Run 1

BOOL

These Run outputs also map to DOP
Instances 1 and 2

4

Get/Set

Run 2

BOOL

7

Get

Running 1

BOOL

8

Get

Running 2

BOOL

9

Get

Ready

BOOL

10

Get

Tripped

BOOL

12

Get/Set

Fault Reset

BOOL

0->1 = Trip Reset

100

Get/Set

Keypad Mode

BOOL

0 = Maintained, 1 = Momentary

101

Get/Set

Keypad Disable

BOOL

0 = Not Disabled, 1= Disabled

Advertising